STC-45
Acoustic Smoke Vents
Cover
& Liner: 14 gauge galvanized steel.
Curb: 14 gauge galvanized steel with 13" self-flashing
curb.
Optional: Double wall curb at exterior.
Hinge: Heavy-duty zinc plated steel with non-removable
pins.
Latch: Positive hold release mechanism designed to
hold the covers closed against 30 lbs./sq. ft. uplift force.
Released by manual pull cables or by fusible melt-out link.
Optional: Electronic/thermal resettable link.
Spring: High pressure gas springs designed to open
vent covers automatically against 10 psf wind or snow load
when released. Double door models come with greased compression
springs enclosed in telescopic tubes.
Hardware: Heavy-duty shock absorbers, continuous extruded
thermal EPDM gasketing, inside and outside manual release
cables.
Insulation: 3" thick acoustic insulation in the
cover and 1.75" in the curb perimeter.
Mounting Flange: 3 1/2" on single wall curb; 2
1/2 " on double wall curb.
UL
Listing: The fusible melt-out link is UL listed. Hatch
UL Listed 793 standard. See size chart for UL/FM listed models.
Finish: Factory applied powder coat.
|